The Rhoss Electa-Ecos-B MHAITI 106 + IUB 06 is a reversible two-section air/water heat pump, with MHAITI 106 outdoor unit and IUB 06 indoor unit, R-32 gas and DC Inverter compressor. With 6 kW Pdesignh at low temperature (35 °C) and class A+++, it produces water up to 60 °C for heating and domestic hot water.

Two-section air/water heat pump

Heating with SCOP 4.54 in class A+++ at 35 °C

In the low-temperature application (35 °C) the heat pump declares Pdesignh of 6 kW, SCOP 4.54 and seasonal energy efficiency ηs of 179 %. In the medium-temperature application (55 °C) the values are 5 kW Pdesignh, SCOP 3.25, ηs of 127 % and class A++. The seasonal data refer to Average climatic conditions according to EN 14825 and to the classification of Regulations (EU) No 811/2013 and No 813/2013.

With outdoor air at 7 °C the heating capacity is 5.9 kW with water at 40-45 °C, power input 1.51 kW and COP 3.91. With water at 30-35 °C the heating capacity rises to 6 kW, with power input 1.2 kW and COP 5.00.

Cooling with EER up to 4.40

In cooling mode, with outdoor air at 35 °C and water at 23-18 °C, the cooling capacity is 5.8 kW with power input of 1.32 kW and EER 4.40. With water at 12-7 °C the cooling capacity is 4.1 kW, with power input of 1.28 kW and EER 3.2. The useful pump head of the circulator is 74 kPa.

Domestic hot water with 3-way valve

The IUB 06 indoor unit includes a 3-way valve for producing domestic hot water, a DHW rapid heating function and an anti-legionella cycle with activation timer. For DHW the system works with outdoor air from -25 °C up to +45 °C.

IUB 06 indoor unit with touch-screen and app

The IUB 06 indoor unit is for wall installation and has an EC circulator, 10 l expansion vessel, 3 bar safety valve, flow switch, water filter and electric backup heater on the system side. The microprocessor control has a touch-screen panel, can alternatively be managed with a room thermostat, and connects via the iOS and Android app or via RS485 with Modbus RTU protocol.

MHAITI 106 outdoor unit with DC Inverter compressor

The MHAITI 106 outdoor unit fits a hermetic twin rotary DC Inverter compressor with vapour injection, with a refrigeration circuit featuring an economiser and an electronic expansion valve. The finned coil has copper tubes and aluminium-manganese fins with Golden Fin treatment, while the DC brushless fan motors adjust the speed continuously. The sound pressure is 37 dB(A) at 5 m in open field.

Frequently asked questions

Which refrigerant gas does the Rhoss Electa-Ecos-B MHAITI 106 + IUB 06 use?
The Rhoss Electa-Ecos-B MHAITI 106 + IUB 06 uses R-32 refrigerant gas, with a DC Inverter compressor.
How is the Rhoss Electa-Ecos-B heat pump controlled?
The Rhoss Electa-Ecos-B is controlled from the touch-screen panel of the IUB 06 indoor unit, or via the iOS and Android app. Alternatively a room thermostat can be used, while with the RS485 Modbus RTU protocol it integrates with other devices.
How noisy is the MHAITI 106 outdoor unit?
The MHAITI 106 outdoor unit has a sound pressure of 37 dB(A) at 5 m in open field.
Does the Rhoss Electa-Ecos-B produce domestic hot water?
Yes, the IUB 06 indoor unit has a 3-way valve for domestic hot water, with DHW rapid heating and an anti-legionella cycle. The system produces water up to 60 °C and works with outdoor air from -25 °C to +45 °C.
How are the MHAITI 106 outdoor unit and IUB 06 indoor unit connected?
The MHAITI 106 outdoor unit (EES01OU002) and the IUB 06 indoor unit (EESB1IU001) are connected by a communication cable and the refrigerant lines, which can be up to 20 m long with a maximum height difference of 15 m. The IUB 06 indoor unit is installed on the wall.

Technical specifications

Model and codes
ModelRhoss Electa-Ecos-B MHAITI 106 + IUB 06
Outdoor unitMHAITI 106 (EES01OU002)
Indoor unitIUB 06 (EESB1IU001)
RefrigerantR-32
First start-upnot included (optional)
Energy efficiency
Pdesignh at 35 °C6 kW
SCOP at 35 °C4.54
Seasonal energy efficiency ηs at 35 °C179 %
Energy class at 35 °CA+++
Pdesignh at 55 °C5 kW
SCOP at 55 °C3.25
Seasonal energy efficiency ηs at 55 °C127 %
Energy class at 55 °CA++
Climatic conditions for seasonal dataAverage according to EN 14825
Energy classificationRegulations (EU) No 811/2013 and No 813/2013
Power and performance
Heating, air 7 °C / water 40-45 °Cheating capacity 5.9 kW
Heating, air 7 °C / water 40-45 °Cpower input 1.51 kW
Heating, air 7 °C / water 40-45 °CCOP 3.91
Heating, air 7 °C / water 30-35 °Cheating capacity 6 kW
Heating, air 7 °C / water 30-35 °Cpower input 1.2 kW
Heating, air 7 °C / water 30-35 °CCOP 5.00
Cooling, air 35 °C / water 12-7 °Ccooling capacity 4.1 kW
Cooling, air 35 °C / water 12-7 °Cpower input 1.28 kW
Cooling, air 35 °C / water 12-7 °CEER 3.2
Cooling, air 35 °C / water 23-18 °Ccooling capacity 5.8 kW
Cooling, air 35 °C / water 23-18 °Cpower input 1.32 kW
Cooling, air 35 °C / water 23-18 °CEER 4.40
Useful circulator pump head74 kPa
Water temperature producedup to 60 °C
Performance declared according to EN 14511
Noise
Outdoor unit sound pressure37 dB(A) at 5 m in open field
Dimensions and weight
MHAITI outdoor unit, width975 mm
MHAITI outdoor unit, height702 mm
MHAITI outdoor unit, depth396 mm
MHAITI outdoor unit, weight55 kg
Indoor unit, width460 mm
Indoor unit, height860 mm
Indoor unit, depth315 mm
Indoor unit, empty weight62 kg
Installation and connections
Power supply230-1-50 V-ph-Hz
Maximum length / height difference of refrigerant lines20 / 15 m
Indoor unit electric heater2 x 1.5 n. x kW
DHW storage temperature probe20 m
RS485 interfaceModbus RTU protocol
Materials
Indoor unit structurezinc-plated and painted sheet steel
Water-side exchangerstainless steel plate type
Outdoor unit structurezinc-plated and painted sheet steel RAL9002
Outdoor unit coilcopper tubes, aluminium-manganese fins, Golden Fin treatment
Functions and equipment
Controltouch-screen, iOS and Android app
Functionsanti-legionella cycle, holiday mode and anti-freeze function, electrical power input limitation function, silent operation with timer, weekly and daily time bands
Management of 2-way on/off valve for isolating part of the system
Unit activation from external contact (remote ON/OFF)
Optional accessories supplied separatelyKSA rubber anti-vibration mounts, KPRE cabling for RS485 serial connection to the touch-screen panel