Skip to content

Description

Rhoss BRIO-I SLIM IXP 40 is an inverter fan coil unit for recessed installation in a false ceiling or on a wall, to be installed with formwork. It cools up to 3.94 kW and heats up to 9.17 kW with water at 70/60 °C. Airflow reaches 648 m³/h, with 27 dB(A) at minimum speed and a depth of 149 mm.

White recessed fan coil unit on a light wall, with supply grille at the top and return grille at the bottom

Cooling: 3.94 kW at MAX, 1.46 kW at MIN

With air at 27 °C and water at 7/12 °C, the total cooling capacity of the Rhoss BRIO-I SLIM IXP 40 is 3.94 kW at MAX speed, 2.9 kW at MED and 1.46 kW at MIN. The fan speed varies continuously, according to the needs of the room.

Heating up to 9.17 kW with water at 70/60 °C

With water at 45/40 °C the heating capacity ranges from 1.79 kW at MIN to 4.46 kW at MAX. With water at 50 °C it reaches 5.43 kW at MAX. With water at 70/60 °C it reaches 9.17 kW at MAX, 6.42 kW at MED and 3.7 kW at MIN.

Quiet at minimum speed: 27 dB(A)

The Rhoss BRIO-I SLIM IXP 40 produces a sound pressure of 27 dB(A) at MIN speed, 37 dB(A) at MED and 45 dB(A) at MAX, measured for a room of 100 m³. The sound power at maximum speed is 54 dB(A).

EC motor: power input from 8 W to 35 W

The EC electronic motor of the tangential fan controls the speed continuously. It draws 8 W at MIN, 17 W at MED and 35 W at MAX, and matches performance to the actual needs of the room.

Radiant function in some versions

In some versions of the range, heat is transferred from the exchanger by a radiating plate, instead of by forced convection alone. During winter operation the front panel warms up and radiates heat. In the version with radiant function, the fan uses low-consumption micro fans.

Slim design and recessed casing

The Rhoss BRIO-I SLIM IXP 40 has a slim design with a simple, essential form. The recessed casing is in galvanised sheet steel, with a vertical auxiliary drain pan and a horizontal drain pan with natural drainage, a washable filter and mounting brackets.

Coil with left-hand ¾" Eurokonus connections

The heat exchanger is a finned coil, with left-hand ¾" Eurokonus connections. Right-hand connections are made with the accessory, supplied separately.

Formwork and decorative panels

The formwork for recessed installation is included only for 2-pipe systems. Decorative panels can be chosen from the wall formwork panel (KPCASEV) and the ceiling formwork panel (KPCASEO), both in matt white RAL 9003, or no panel at all.

Frequently asked questions

What is the radiant function of the Rhoss BRIO-I SLIM IXP 40?
In some versions of the Rhoss BRIO-I SLIM IXP 40 range, heat is transferred by a radiating plate, and the front panel warms up during winter operation, radiating heat.
Which version of the Rhoss BRIO-I SLIM IXP 40 is described on this page?
This page describes the 2T version with a single main coil, with formwork included only for 2-pipe systems. The 4T version is 639 mm high, compared with 579 mm for the 2T.
How noisy is the Rhoss BRIO-I SLIM IXP 40 at minimum speed?
At MIN speed the Rhoss BRIO-I SLIM IXP 40 produces 27 dB(A) of sound pressure for a room of 100 m³, compared with 37 dB(A) at MED and 45 dB(A) at MAX.
How much energy does the Rhoss BRIO-I SLIM IXP 40 consume?
The EC motor of the Rhoss BRIO-I SLIM IXP 40 draws 8 W at MIN, 17 W at MED and 35 W at MAX, with a power supply of 230V - 1ph - 50Hz.
What material is the recessed casing of the Rhoss BRIO-I SLIM IXP 40 made from?
The recessed casing of the Rhoss BRIO-I SLIM IXP 40 is made of galvanised sheet steel, with a drain pan, washable filter and mounting brackets.

Technical specifications

Model and codes
ModelRHOSS Fan Coil Inverter Fan Coil Unit BRIO-I SLIM IXP 40 - Recessed for False Ceiling/Wall with Formwork
Typehorizontal/vertical recessed unit for false ceiling or wall
Version2T, single main coil
Decorative panelnone, or wall formwork (KPCASEV) or ceiling formwork (KPCASEO), matt white RAL 9003
Power and performance
Total cooling capacity MAX (air 27 °C, water 7/12 °C)3.94 kW
Total cooling capacity MED2.9 kW
Total cooling capacity MIN1.46 kW
Heating capacity water 45/40 °C, MAX4.46 kW
Heating capacity water 45/40 °C, MED3.11 kW
Heating capacity water 45/40 °C, MIN1.79 kW
Heating capacity water 50 °C, MAX5.43 kW
Heating capacity water 50 °C, MED3.73 kW
Heating capacity water 50 °C, MIN1.87 kW
Heating capacity water 70/60 °C, MAX9.17 kW
Heating capacity water 70/60 °C, MED6.42 kW
Heating capacity water 70/60 °C, MIN3.7 kW
Air and noise
Airflow MAX648 m³/h
Airflow MED494 m³/h
Airflow MIN426 m³/h
Sound pressure per room of 100 m³, MAX45 dB(A)
Sound pressure per room of 100 m³, MED37 dB(A)
Sound pressure per room of 100 m³, MIN27 dB(A)
Sound power MAX54 dB(A)
Electrical
Power supply230V - 1ph - 50Hz
Power input MAX35 W
Power input MED17 W
Power input MIN8 W
Dimensions and weight
Width1523 mm
Height 2T version579 mm
Height 4T version639 mm
Depth149 mm
Weight 2T version29 kg
Weight 4T version32 kg
Construction and connections
Casinggalvanised sheet steel with vertical auxiliary and horizontal drain pan with natural drainage, washable filter and mounting brackets
Heat exchangerfinned coil
Fantangential, with EC electronic motor
Left-hand connections¾" Eurokonus
Right-hand connectionsaccessory supplied separately
Formworkincluded only for 2-pipe systems
Functions
Functionsinverter with continuous speed control; radiant function in some versions of the range