Rhoss
RHOSS Fan Coil Unit Inverter BRIO-I SLIM IXP 30 - Recessed for False Ceiling/Wall With Casing Box

What size do I need?
For heat pumps and fan coils the right output is worked out by the installer on your home: heat loss, system, climate zone. Send us your measurements and we will reply with a quote.
Couldn't load pickup availability
Shipping and delivery
Shipping and delivery
Timing. With online payment, your order leaves with express courier and arrives within 1-2 working days. In remote areas and on islands, a few extra days may be needed: the estimated delivery date for your postcode is shown under “When it arrives”.
Costs. For orders under €80, shipping costs €8. Delivery to your floor is available for an additional charge.
Availability. Each product shows whether it is in stock, whether only a few units are left, or whether it is sold out; for sold-out products, you can leave your email and we will let you know as soon as they are back in stock.
Your order. You can track it from your account. For any questions, you will find our contact details on the Contact page; all the terms are on the Shipping page.
Support before and after purchase
Support before and after purchase
For advice on choosing a product, a technical question or an order already placed, the Buytutto customer service team is available Monday to Friday, 9:00 am to 1:00 pm and 2:00 pm to 6:00 pm.
You can message us on WhatsApp using the button on this page, or use the contact details on the Contact page. For a product you have already received, open a request from the Support page.
Description
The Rhoss BRIO-I SLIM IXP 30 is a concealed inverter fan coil unit for false ceiling or wall installation, with a mounting box, i.e. a unit that air-conditions with air and heats with water. Key figures to check when choosing: 3.31 kW maximum cooling capacity, 3.75 kW maximum heating capacity with water at 45/40 °C, 26 dB(A) at minimum speed, 149 mm depth and a continuously adjustable EC motor.
EC motor: consumption from 8 W to 28 W
The tangential fan is driven by an electronic EC motor with continuously variable speed, which matches the performance to the actual needs of the room. The EC motor draws 8 W at minimum speed, 15 W at medium and 28 W at maximum.
Quiet at minimum speed: 26 dB(A)
Based on a sound pressure measured for a 100 m³ room, the BRIO-I SLIM is at 26 dB(A) at minimum speed, 37 dB(A) at medium and 45 dB(A) at maximum. The sound power at maximum is 54 dB(A).
Cooling and heating across three speeds
In cooling mode (air 27 °C, water 7/12 °C) the total cooling capacity is 3.31 kW at MAX, 2.43 kW at MED and 1.27 kW at MIN. In heating, the heating capacity is 3.75 kW at MAX with water at 45/40 °C, 4.51 kW with water at 50 °C and 7.54 kW with water at 70/60 °C.
Radiant function in some versions of the range
In some versions of the Brio I-Slim range, heat is transferred from the exchanger via a plate by radiation, rather than by forced convection alone. The front panel warms up during winter operation.
Recessed for false ceiling or wall, with mounting box included in the 2-pipe version
The BRIO-I SLIM IXP 30 is a recessed unit for installation in a false ceiling or on a wall, with a depth of 149 mm and a width of 1323 mm. The mounting box for recessed installation is included in the 2-pipe version. As a decorative panel, you can choose between the wall panel or the ceiling panel for the mounting box, both matt white RAL 9003, or no panel at all.

Finned-tube coil with Eurokonus connections
The exchanger is a finned-tube coil with left-hand connections of ¾" Eurokonus. The right-hand connections are fitted with an accessory supplied separately. The 2T version has a single main coil.
Regenerable filter and condensate tray
The galvanised sheet steel structure includes a vertical condensate tray, an additional horizontal condensate tray with natural drainage, a regenerable filter and mounting brackets.
Frequently asked questions
Which spaces is the Rhoss BRIO-I SLIM IXP 30 suitable for?
Is a mounting box needed to install the BRIO-I SLIM IXP 30?
What is the difference between the 2-pipe and 4-pipe versions?
How noisy is the BRIO-I SLIM IXP 30?
What is the radiant function of the Rhoss BRIO-I SLIM?
How much energy does the Rhoss BRIO-I SLIM IXP 30 use?
Technical specifications
| Model and codes | |
| Model | Rhoss BRIO-I SLIM IXP 30 |
| Type | concealed inverter fan coil unit for false ceiling or wall, with mounting box |
| Version | 2-pipe (2T) with single main coil; 4-pipe (4T) |
| Wall decorative panel for mounting box | KPCASEV, matt white RAL 9003 |
| Ceiling decorative panel for mounting box | KPCASEO, matt white RAL 9003 |
| Power and performance | |
| Total cooling capacity MAX (air 27 °C, water 7/12 °C) | 3.31 kW |
| Total cooling capacity MED | 2.43 kW |
| Total cooling capacity MIN | 1.27 kW |
| Heating capacity MAX (water 45/40 °C) | 3.75 kW |
| Heating capacity MED (water 45/40 °C) | 2.75 kW |
| Heating capacity MIN (water 45/40 °C) | 1.48 kW |
| Heating capacity MAX (water 50 °C) | 4.51 kW |
| Heating capacity MED (water 50 °C) | 3.23 kW |
| Heating capacity MIN (water 50 °C) | 1.56 kW |
| Heating capacity MAX (water 70/60 °C) | 7.54 kW |
| Heating capacity MED (water 70/60 °C) | 5.52 kW |
| Heating capacity MIN (water 70/60 °C) | 2.97 kW |
| Airflow and noise | |
| Air flow rate MAX | 576 m³/h |
| Air flow rate MED | 453 m³/h |
| Air flow rate MIN | 370 m³/h |
| Sound pressure for 100 m³ room MAX | 45 dB(A) |
| Sound pressure for 100 m³ room MED | 37 dB(A) |
| Sound pressure for 100 m³ room MIN | 26 dB(A) |
| Sound power MAX | 54 dB(A) |
| Electrical data | |
| Power supply | 230V - 1ph - 50Hz |
| Power input MAX | 28 W |
| Power input MED | 15 W |
| Power input MIN | 8 W |
| Dimensions and weights | |
| Width | 1323 mm |
| Height 2-pipe version (2T) | 579 mm |
| Height 4-pipe version (4T) | 639 mm |
| Depth | 149 mm |
| Weight 2T version | 26 kg |
| Weight 4T version | 28 kg |
| Installation and equipment | |
| Exchanger | finned-tube coil, left-hand connections ¾" Eurokonus; right-hand connections with accessory supplied separately |
| Fan | tangential with EC electronic motor |
| Structure | galvanised sheet steel with condensate tray, regenerable filter and mounting brackets |
| Included | mounting box for recessed installation (2-pipe systems only) |
| Radiant function | available in some versions of the range |