Skip to content

Description

Beretta HYDRO UNIT M 006 is a single-phase air-to-water hydronic heat pump with R-32 refrigerant, for heating, cooling and domestic hot water with storage tanks or solar kits. In heating mode it delivers 6.35 kW of useful output with water at 35 °C and a COP of 4.95, with energy class A+++ up to 35 °C. In cooling mode, useful output reaches 7.00 kW with water at 7 °C.

Two white outdoor units of an air-to-water heat pump

System combinations

The heat pump can be combined with fan coil units, underfloor heating, high-efficiency low-temperature radiators, domestic hot water tanks and solar kits, all supplied on site.

HYDRO UNIT M series: ten models from 4 to 16 kW

The HYDRO UNIT M series includes ten models with outputs from 4 kW to 16 kW, with a fast response to demand and reduced energy consumption. Class A+++ applies up to 35 °C and A++ up to 55 °C.

Twin rotary compressor and inverter board

The twin rotary compressor is a DC double rotary compressor. Together with the fan motor and the pump, it works with the Inverter System and precisely controls motor speed, delivering the power needed for the actual load and saving energy. The inverter control board maximises output under critical load conditions and ensures stability and efficiency at partial loads.

Electronic expansion valve and operating parameters board

The electronic expansion valve optimises the flow of refrigerant in every situation. The operating parameters control board constantly monitors ambient and water temperature to activate the various components and meet demand.

Special blade fan and aluminium coil

The fan has a specially designed blade that optimises the airflow surface, improves efficiency and reduces fan noise. The heat exchange coil has an extended surface and aluminium fins.

AISI 316 stainless steel plate heat exchanger

The AISI 316 stainless steel plate heat exchanger is protected by closed-cell anti-condensation insulation and offers high heat exchange efficiency.

Hydronic kit and hydronic module

The hydronic kit is supplied with the monoblock and contains all the essential components for installation. The hydronic module includes a low-consumption circulator pump, an 8-litre expansion vessel, an automatic air vent and a safety valve. The maximum operating pressure of the hydronic circuit is 3 bar.

Outdoor installation with anti-freeze function

The HYDRO UNIT M 006 is designed for outdoor installation. The anti-freeze function, which can be programmed by the customer, activates automatically when the water temperature in the system drops below a preset value, protecting the entire hydraulic circuit.

White outdoor unit of a heat pump installed on a wooden terrace, next to a large glass window

Quiet Mode

The low noise level comes from its construction features and can be further reduced with the Quiet Mode, which can be programmed by the customer.

Backup heater available as an accessory

The backup heater, available as an accessory, increases heating capacity when outdoor temperatures are cold. It also serves as a backup in case of an operating fault and as frost protection for the external water pipes during winter.

R-32 and HP KEYMARK certification

R-32 gas has a lower Global Warming Potential than traditional gases. The sealed circuit for fluorinated gases, the reduced refrigerant charge volumes and lower CO2 emissions increase the environmental sustainability of the HYDRO UNIT M. The design meets the requirements of the voluntary European HP KEYMARK certification.

Frequently asked questions

What systems is the Beretta HYDRO UNIT M 006 used for?
The Beretta HYDRO UNIT M 006 is used for heating, cooling and domestic hot water with storage tanks or solar kits. It combines with fan coil units, underfloor heating, high-efficiency low-temperature radiators and solar kits, all supplied on site.
Does the Beretta HYDRO UNIT M 006 need to be installed outdoors?
Yes, the HYDRO UNIT M 006 is designed for outdoor installation. Its anti-freeze function, which can be programmed by the customer, activates automatically when the water temperature drops below a preset value.
Which refrigerant gas does the HYDRO UNIT M 006 use?
The HYDRO UNIT M 006 uses R-32 gas, which has a lower Global Warming Potential than traditional gases, and is installed in a sealed circuit for fluorinated gases.
How quiet is the Beretta HYDRO UNIT M 006?
The low noise level of the HYDRO UNIT M 006 comes from its construction features and can be reduced further with the Quiet Mode, which can be programmed by the customer. The special blade fan also helps reduce fan noise.
What is the backup heater of the HYDRO UNIT M 006 for?
The backup heater, available as an accessory, increases heating capacity when outdoor temperatures are cold. It also acts as a backup in case of an operating fault and protects the external water pipes from frost during winter.
What is the difference between a hydronic kit and a hydronic module?
The hydronic kit is supplied with the monoblock and contains the essential components for installation. The hydronic module of the HYDRO UNIT M 006 includes a low-consumption circulator pump, an 8-litre expansion vessel, an automatic air vent and a safety valve.

Technical specifications

Model and codes
ModelHYDRO UNIT M 006
Typeair-to-water hydronic heat pump, monoblock
Power supplysingle-phase
RefrigerantR-32
Energy efficiency
Heating energy class with water at 35 °CA+++
Heating energy class with water at 55 °CA++
Heating COP with water at 35 °C4.95
Heating COP with water at 45 °C3.70
Heating COP with water at 55 °C2.95
Cooling EER with water at 7 °C3.00
Cooling EER with water at 18 °C4.80
Power and performance
Useful heating output with water at 35 °C6.35 kW
Useful heating output with water at 45 °C6.30 kW
Useful heating output with water at 55 °C6.00 kW
Heating power input with water at 35 °C1.28 kW
Heating power input with water at 45 °C1.70 kW
Heating power input with water at 55 °C2.03 kW
Useful cooling output with water at 7 °C7.00 kW
Useful cooling output with water at 18 °C6.50 kW
Cooling power input with water at 7 °C2.33 kW
Cooling power input with water at 18 °C1.35 kW
Features
Maximum operating pressure of hydronic circuit3 bar
Maximum power input0.043 kW
System expansion vessel8 litres
CertificationHP KEYMARK
Dimensions and weight
Dimensions (L x H x D)1295x792x429 mm
Empty weight98.0 kg