Skip to content

Description

The GEL Boiler Cleaner E is a concentrated acid-based liquid descaler, made by GEL, for removing limescale and corrosion residues in heating systems, heat exchangers and copper cooling circuits. It contains corrosion inhibitors, antifoam agents and a exhaustion indicator. It is used diluted in water at a 10-20% dosage, with a pH < 1 and a specific gravity of 1.15 kg/dm³.

10-20% dilution: the colour tells you when to stop

The product is diluted in water at 10-20%, that is 1-2 litres of product in 10 litres of water, starting from the lowest concentration. When the solution changes from red to orange-yellow, becomes cloudy or stops fizzing, add more Boiler Cleaner E until the red acid solution no longer produces bubbles.

Copper only: strongly corrosive on other metals

The GEL Boiler Cleaner E is intended for copper heat exchangers. Do not use it on stainless steel, aluminium, zinc, tin and light alloys, which it attacks strongly.

Neutralisation after descaling and use with Boy C pump

After descaling, a neutralising wash is recommended to remove residual acidity with a 3-5% solution of Boiler Cleaner N, then rinse with running water. If you use a Boy C series pump, remove the tank cap to vent the gases produced during the operation, that is carbon dioxide.

Warning: strongly acidic product

The Boiler Cleaner E is strongly acidic: protect your eyes and skin with goggles and gloves. If it splashes on your skin, rinse the affected areas with water containing 1-2% Boiler Cleaner N or sodium bicarbonate.

Store in a ventilated room, protected from frost

Store the GEL Boiler Cleaner E in a ventilated room, away from heat sources and protected from frost, out of reach of children.

Frequently asked questions

What is the GEL Boiler Cleaner E used for?
The GEL Boiler Cleaner E removes limescale and corrosion residues in heating systems, heat exchangers and copper cooling circuits.
Which metals can the GEL Boiler Cleaner E be used on?
The GEL Boiler Cleaner E is intended for copper only: it attacks stainless steel, aluminium, zinc, tin and light alloys strongly.
What concentration should the GEL Boiler Cleaner E be diluted to?
The GEL Boiler Cleaner E is diluted in water at 10-20%, that is 1-2 litres of product in 10 litres of water, starting from the lowest concentration.
How do you tell when descaling is finished?
With the GEL Boiler Cleaner E, the solution changes colour from red to orange-yellow; descaling is finished when the red acid solution no longer produces bubbles, then it is neutralised with 3-5% Boiler Cleaner N.
What should you do if GEL Boiler Cleaner E splashes on your skin?
Rinse the affected areas with water containing 1-2% Boiler Cleaner N or sodium bicarbonate, since the GEL Boiler Cleaner E is strongly acidic.
Where should the GEL Boiler Cleaner E be stored?
The GEL Boiler Cleaner E should be stored in a ventilated room, away from heat sources, protected from frost and out of reach of children.

Technical specifications

ModelGEL Boiler Cleaner E - Descaler for copper heat exchangers
Product code113.005.30
Pack size10 litres
ΔP0.2 bar
Dosage10-20%
pH< 1
Specific gravity1.15 kg/dm³
UseTechnical / Potable
Water temperature (min-max)5 °C - 40 °C
Ambient temperature (min-max)5 °C - 50 °C