Skip to content

Description

The Ferroli Force W 80 (code 0MDSCAWA) is a high-power condensing boiler for heating only, designed for new builds and for renovating plant rooms. It has ERP energy class A and an efficiency of 98.3% at 80-60 °C. Each module works on its own or in a cascade of up to four units.

Illustrated panels showing the main features of a condensing boiler: heating account incentive, tax deduction

Up to 4 modules in cascade with INAIL certification

Each module is installed individually or in configurations of up to four units in cascade, with INAIL certification, for a maximum combined output of 600 kW. Complete hydraulic, gas and flue accessories are provided for configurations of 2, 3 or 4 modules.

White wall-mounted boiler with white flue outlet at the top and dark control panel at the bottom

Monobloc heat exchanger in aluminium-silicon alloy

The monobloc heat exchanger in aluminium-silicon alloy is designed to deliver maximum exchange efficiency and low pressure losses on the water circuit.

Metal fibre micro-flame burner, class 6

The premix combustion unit uses a metal fibre burner with a micro-flame, with very low pollutant emissions: class 6 according to EN 15502-1. The modules run on natural gas or LPG.

Protections with constant ΔT sensors and flue gas safety

The flow and return sensors work at constant ΔT. The heat exchanger is protected against overtemperature, calibrated at 95 °C. The flue gas safety sensor and the water pressure switch, with a minimum threshold of 0.8 bar, complete the protection.

Sealed-chamber air/flue circuit B23, C13 and C33

The air/flue circuit of the Ferroli Force W 80 is sealed-chamber, certified B23, C13 and C33. A non-return clapet valve on the flue exhaust duct makes it possible to size the pressurised manifold.

Hydraulic group supplied as an accessory

The hydraulic group is supplied as an accessory and has isolation valves, one of which is a three-way valve for venting to atmosphere. It can be configured with two circulation pumps, standard or high-head.

Efficiency up to 108.6% at reduced load and incentives

Efficiency is 98.3% at 80-60 °C and 104.8 / 108.5% at 50-30 °C (max / min), with 108.6% at 30% reduced load. Its efficiency allows access to the economic incentives available for energy renovation of climate systems.

Frequently asked questions

What fuel does the Ferroli Force W 80 use?
The Ferroli Force W 80 runs on natural gas or LPG: its modules can run on either fuel.
How many Ferroli Force W 80 boilers can be connected in cascade?
The Ferroli Force W 80 can be installed singly or in a cascade of up to four units, with INAIL certification, for a maximum combined output of 600 kW.
What NOx emission class does the Ferroli Force W 80 have?
The Ferroli Force W 80 has NOx emission class 6 according to EN 15502-1, thanks to its metal fibre micro-flame burner.
Does the Ferroli Force W 80 have a sealed-chamber circuit?
Yes, the Ferroli Force W 80 has a sealed-chamber air/flue circuit certified B23, C13 and C33.
How much does the Ferroli Force W 80 weigh and what are its dimensions?
The Ferroli Force W 80 has a net weight of 67 kg and dimensions W x H x D of 610 x 900 x 460.
Is the hydraulic group included with the Ferroli Force W 80?
The hydraulic group of the Ferroli Force W 80 is supplied as an accessory and can be configured with two circulation pumps, standard or high-head.

Technical specifications

Model and codes
Model0MDSCAWA W 80
ERP classA
NOx emission class6
Degree of protectionIPX4D
Output and performance
Heating thermal input, max74.00 kW
Heating thermal input, min15.0 kW
Heating thermal output 80°C-60°C, max72.9 kW
Heating thermal output 80°C-60°C, min14.7 kW
Useful thermal output 50°C-30°C, max77.00 kW
Useful thermal output 50°C-30°C, min16.3 kW
Efficiency 80°C-60°C, max98.3 %
Efficiency 80°C-60°C, min98.3 %
Efficiency 50°C-30°C, max104.8 %
Efficiency 50°C-30°C, min108.5 %
Reduced load 30%108.6 %
Heating operating pressure, max6 bar
Heating operating pressure, min0.8 bar
Water, gas and power supply
Heating water content4.2 l
Fuelnatural gas or LPG
Supply voltage230 V / 50 Hz
Dimensions and weight
Net weight67 kg
Dimensions (W x H x D)610 x 900 x 460