Ideal Clima
Ceiling Fan Coil Unit Ideal Clima Falko OC Standard 850 Cod. TCM08A - Controller Not Included
- Class A

What size do I need?
For heat pumps and fan coils the right output is worked out by the installer on your home: heat loss, system, climate zone. Send us your measurements and we will reply with a quote.
Couldn't load pickup availability
Shipping and delivery
Shipping and delivery
Timing. With online payment, your order leaves with express courier and arrives within 1-2 working days. In remote areas and on islands, a few extra days may be needed: the estimated delivery date for your postcode is shown under “When it arrives”.
Costs. For orders under €80, shipping costs €8. Delivery to your floor is available for an additional charge.
Availability. Each product shows whether it is in stock, whether only a few units are left, or whether it is sold out; for sold-out products, you can leave your email and we will let you know as soon as they are back in stock.
Your order. You can track it from your account. For any questions, you will find our contact details on the Contact page; all the terms are on the Shipping page.
Support before and after purchase
Support before and after purchase
For advice on choosing a product, a technical question or an order already placed, the Buytutto customer service team is available Monday to Friday, 9:00 am to 1:00 pm and 2:00 pm to 6:00 pm.
You can message us on WhatsApp using the button on this page, or use the contact details on the Contact page. For a product you have already received, open a request from the Support page.
Description
The ceiling fan coil unit Ideal Clima Falko OC Standard 850 TCM08A (fan coil for false ceilings) heats, cools and dehumidifies rooms. The control is not included in the supply. Total cooling capacity 4,460 W at 7 °C, heating capacity 5,375 W at 45 °C, maximum airflow 850 m³/h, maximum sound pressure 46 dB(A) and height 24 cm.

24 cm height for the false ceiling
With a height of 24 cm and a high-efficiency heat exchange coil, the Falko OC can be installed inside false ceilings in residential settings. The frame is galvanised sheet steel.

Reversible air return on site
The rear air return can be converted on site to bottom return with a simple screwdriver. It can be ducted to individual rooms or drawn in through a single grille beneath the unit. The air filter is removable and located on the return, while the condensate drip tray has a DN 20 outlet.
Ducted network with modular plenums
The Falko OC allows simple ducted networks to be built for distributing air to all rooms, with the range of accessories available. These include modular supply and return plenums with push-fit spigots.

Three-speed control
The motor has three live-phase inputs for speed selection. The Falko OC is operated by a three-speed timer thermostat built into the wall or by a generic three-speed fan coil thermostat capable of supplying live-phase contacts.

Pairing with boilers and heat pumps
The Falko OC pairs with standard boilers, condensing boilers, solar systems and heat pumps. It delivers heat output with high efficiency at both high and low flow temperatures, making it ideal for heat pump systems.
Frequently asked questions
Can the Falko OC be installed in a false ceiling?
Which controls does the Falko OC work with?
Can the air return be changed from rear to bottom?
Which systems does the Falko OC pair with?
Where are the water connections on the Falko OC?
Can the air filter of the Falko OC be removed?
Technical specifications
| Model and codes | |
| Model | Ceiling Fan Coil Unit Ideal Clima Fancoil Falko OC Standard 850 TCM08A Control Not Included |
| Code | TCM08A |
| GTIN | 8029094462978 |
| Output and performance | |
| Total cooling capacity at 7 °C | 4,460 W |
| Sensible cooling capacity | 3,229 W |
| Heating capacity at 45 °C | 5,375 W |
| Airflow at max speed at 30 Pa | 850 m³/h |
| Sound pressure at max speed | 46 dB(A) |
| Water and hydraulics | |
| Water flow in cooling | 12 l/min |
| Water flow in heating | 15 l/min |
| Pressure drop Falko OC only in cooling | 37 kPa |
| Pressure drop 2- and 3-way valves KVs=1.7 in cooling | 3.6 kPa |
| Pressure drop Falko OC in heating | 54 kPa |
| Pressure drop 3-way valve KVs=1.7 in heating | 5.3 kPa |
| Water connections | 3/4” F, left side, reversible on site |
| Condensate outlet | DN 20 |
| Installation and equipment | |
| Height | 24 cm |
| Frame | galvanised sheet steel |
| Air return | convertible on site from rear to bottom |
| Air filter | removable, on the return |
| Motor | three live-phase inputs for speed selection |
| Control | not included |